Push-Fit fluid temperature sensor for Gas Boilers

Short Description:

This probe is designed for use in gas boiler applications, it’s a push-fit or clip-in temperature sensor in a brass housing fitted with integral o-ring. they can be used anywhere that you want to sense or control temperature of a liquid in a pipe. Built-in NTC thermistor or PT element, various industry standard connector types are available.


Product Detail

Product Tags

Immersion Temperature Sensor for Wall-Mounted Boiler

A very typical screw-in fluid temperature sensor which originally designed for use in gas boiler applications, with a 1/8″BSP thread and integral plug-in locking connector. can be used anywhere that you want to sense or control temperature of a liquid in a pipe, Built-in NTC thermistor or PT element, various industry standard connector types are available.

Features:

 Miniature, immersible, and Fast thermal response
 To install and fixed by screw thread (G1/8" thread) , easy to install, size can be customized
 A glass thermistor is sealed with epoxy resin, Suitable for use in high humidity and high moisture conditions
 Proven long term Stability and Reliability ,Excellent performance of voltage resistance
 Housings could be Brass, Stainless steel and plastic
 Connectors could be Faston, Lumberg, Molex, Tyco

Applications:

 Wall-hanging stove, Water Heater
 Hot water boiler tanks
 Automobile engines (solid), engine oil (oil), radiators (water)
Automobile or motorcycles ,the Electronic fuel injection
 Measuring oil / coolant temperature

Characteristics:

1. Recommendation as follows:
R25℃=10KΩ±1% B25/50℃=3950K±1% or
R25℃=50KΩ±1% B25/50℃=3950K±1% or
R25℃=100KΩ±1% B25/50℃=3950K±1%
2. Working temperature range: -30℃~+105℃
3. Thermal time constant: MAX. 10sec.
4. Insulation voltage: 1800VAC, 2sec.
5. Insulation resistance: 500VDC ≥100MΩ
6. Above characteristics all can be customized

Dimensions:

size MFL-1

Product specification:

Specification
R25℃
(KΩ)
B25/50℃
(K)
Disspation Constant
(mW/℃)
Time Constant
(S)
Operation Temperature

(℃)

XXMFL-10-102□ 1 3200
approx. 2.2 typical in still air at 25℃
5 - 9    typical in stirred water
-30~105
XXMFL-338/350-202□
2
3380/3500
XXMFL-327/338-502□ 5 3270/3380/3470
XXMFL-327/338-103□
10
3270/3380
XXMFL-347/395-103□ 10 3470/3950
XXMFL-395-203□
20
3950
XXMFL-395/399-473□ 47 3950/3990
XXMFL-395/399/400-503□
50
3950/3990/4000
XXMFL-395/405/420-104□ 100 3950/4050/4200
XXMFL-420/425-204□ 200 4200/4250
XXMFL-425/428-474□
470
4250/4280
XXMFL-440-504□ 500 4400
XXMFLS-445/453-145□ 1400 4450/4530